Fire-resistant FTG18M16 flexible cable designed for maximum safety in case of fire. Ideal for electrical systems in critical environments. With LS0H sheathing and fire resistance up to 120 minutes at 820°C, it is perfect for emergency and safe power systems, with the following features:
Section: 1x70 sq mm
Conductor diameter: 10.5 mm
Insulation thickness: 1.4 mm
Sheath thickness: 1.6 mm
Outer diameter: 19.2 mm
Electrical resistance: 0.272 ohm/km
Current carrying capacity: 222A in pipe, 268A in free air
Rated voltage: 0.6/1 kV
The selling price is per meter.
(modificale nel modulo Rassicurazioni cliente)
(modificale nel modulo Rassicurazioni cliente)
(modificale nel modulo Rassicurazioni cliente)
The FTG18M16 cable is designed to maintain power in emergency conditions. It complies with IEC 20-67 standards, providing fire resistance for up to 120 minutes at 820°C, making it ideal for emergency lights, fire extinguishing systems and safety devices.
Suitable for fixed installation indoors and outdoors, even in wet conditions, it can be installed on masonry, metal structures, catwalks and conduits, as well as buried without additional protection.
With its low electrical resistance (0.272 ohm/km) and high current carrying capacity, this cable ensures reliability and safety in the most demanding electrical distribution systems.
| Feature | Value |
|---|---|
| Conductor | Flexible annealed red copper cord, class 5 |
| Tape | Glass/mica helically wound |
| Insulator | Rubber compound, G18 quality |
| Filler | Compound of nonhygroscopic material |
| Outer sheath | LS0H compound, M16 quality |
| Sheath color | Blue |
| Fire resistance | 120 minutes at 820°C |
| Rated voltage Uo/U | 0.6/1 kV |
| Maximum operating temperature | 90°C |
| Minimum operating temperature | -15°C |
| Minimum laying temperature | -5°C |
| Maximum short-circuit temperature | 250°C |
| Maximum tensile stress | 50 N/mm² |
| Minimum bending radius | 14 times maximum outer diameter |
| Conductor diameter | 10.5 mm |
| Insulation thickness | 1.4 mm |
| Sheath thickness | 1.6 mm |
| Outer diameter | 19.2 mm |
| Electrical resistance | 0.272 ohm/km |
| Current flow rate in tube in air | 222A |
| Current flow rate in free air | 268A |
check_circle
check_circle
Comments (0)
Your review appreciation cannot be sent
Report comment
Report sent
Your report cannot be sent