Flexible power cable FTG18OM16 with HEPR G18 insulation and LSZH M16 sheathing, designed to ensure maximum safety against fire. Ideal for critical installations and civil infrastructure, with the following characteristics:
Conductor diameter: 13.3 mm
Insulation thickness: 1.6 mm
Outer diameter: 21.6 mm
Electrical resistance: 0.206 Ohm/km
Current carrying capacity in pipe in air: 269 A
Underground current carrying capacity: 217 A
The selling price is intended per meter.
(modificale nel modulo Rassicurazioni cliente)
(modificale nel modulo Rassicurazioni cliente)
(modificale nel modulo Rassicurazioni cliente)
FTG18OM16 flexible energy cable is designed to ensure optimal performance and maximum safety in the most critical environments. Certified according to the Construction Products Regulation, this cable ensures fire resistance for up to 120 minutes at 830 degrees, limiting the production of toxic and corrosive fumes. Its structure makes it ideal for electrical installations in civil and industrial buildings where it is essential to ensure continuity of operation even in case of fire.
The cable is made of high-performance materials to ensure strength and safety:
Class 5 annealed red copper conductor, highly flexible for easy laying
Mica fire barrier, which protects the conductor from intense heat
Insulation made of HEPR G18, a high-modulus elastomeric rubber that provides excellent mechanical and thermal protection
Filler made of non-fibrous, non-hygroscopic material to prevent moisture infiltration
LSZH M16 (Low Smoke Zero Halogen) sheathing, which minimizes the spread of fire and the emission of toxic fumes
Designed to withstand demanding operating conditions, with a rated voltage of 0.6/1 kV AC - 1.8 kV DC and a test voltage of up to 4000V. Its thermal characteristics make it ideal for high-temperature applications:
Maximum operating temperature: +90°C
Maximum short circuit temperature: up to +250°C (cross-sections ?240 mm²)
Electrical resistance: 0.206 Ohm/km
Current carrying capacity: 269 A in pipe in air, 217 A buried
In addition, it can withstand a maximum pull stress of 50 N/mm² during installation, with a minimum bending radius of 12 times the outside diameter (12D) for safe and efficient installation.
Due to its advanced construction and fire-resistant features, it is ideal for:
Powering electrical systems in civil and industrial buildings
Fire and security systems in public places
Electrical systems in tunnels, tunnels, subways, airports and railway stations
Laying in indoor and outdoor environments, including wet (AD6)
Installations on masonry, metal structures, gutters, walkways and suspended
Direct or indirect underground laying, ensuring versatility and safety
| Feature | Value |
|---|---|
| Conductor | Flexible annealed red copper (Class 5) |
| Insulation | HEPR rubber G18 |
| Filler | Non-fibrous and non-hygroscopic material |
| Outer sheathing | LSZH M16 (blue) |
| Rated voltage | 600V (AC) / 1800V (DC) |
| Rated voltage | 1kV (AC) / 1.8kV (DC) |
| Maximum voltage | 1.2kV (AC) / 1.8kV (DC) |
| Test voltage | 4000V |
| Operating temperature | -15°C / +90°C |
| Minimum laying temperature | 0°C |
| Minimum bending radius | 12D |
| Conductor diameter | 13.3 mm |
| Insulation thickness | 1.6 mm |
| Outer diameter | 21.6 mm |
| Electrical resistance | 0.206 Ohm/km |
| Current flow rate in tube in air | 269 A |
| Current flow rate buried | 217 A |