Siemens surge arrester for protecting electrical systems in TN-S and TT systems, ideal for industrial and residential installations, with DIN rail mounting NS 35 with the following features:
Type 2, Requirement Class C, UC 350V
3+1-pole circuit for TN-S and TT systems, 3+N/PE configuration
Discharge current per phase up to 40 kA (8/20 µs), discharge current 20 kA
DIN rail mounting NS 35, compact with width 71.5 mm
Rated voltage (UC): 350 V
Supports a rated voltage of 350 V and is ideal for industrial and residential installations. It offers an IP20 degree of protection and an insulation resistance of 1000 M.
(modificale nel modulo Rassicurazioni cliente)
(modificale nel modulo Rassicurazioni cliente)
(modificale nel modulo Rassicurazioni cliente)
The surge arrester is designed to protect against transient overvoltages in TN-S and TT systems, with a 4-pole (3+1) configuration for effective protection management. It supports operating voltages up to 230 V AC with a frequency of 50/60 Hz and can discharge impulse currents up to 40 kA per phase.
Featuring a compact design of 4 U.M, this arrester is designed to be mounted on NS 35 DIN rail. The insulation resistance of 1000 M? ensures system safety and reliability over time.
With an IP20 rating, the arrester can operate in environments with relative humidity between 5 and 95 percent and operating temperatures between -40 and +80 degrees. It is vibration resistant and suitable for installations at altitudes up to 2,000 m.
Detailed technical specifications:
Type: Type 2, Class C
Rated voltage: 350 V UC
Pole configuration: 3+1 circuit, 3+N/PE
Operating voltage: 230 V AC, 50/60 Hz
Discharge current: up to 40 kA per phase (8/20 µs)
Degree of protection: IP20
Pollution degree 2
Adjustable trip current trip factor 1.6
Stripping length 16 mm
Insulation resistance: 1000 M
Dimensions: Width 71.5 mm, Height 90 mm, Depth 71.5 mm
Operating temperature: -40/+80 degrees
Relative humidity: 5 ... 95%
Connection: Screw clamp, stripping length 16 mm, tightening torque 4.3 ... 4.7 Nm
Conductor cross-section: flexible conductors 1.5 to 25 mm², rigid conductors 1.5 to 35 mm²