Legrand TRIMOD HE 10 kVA three-phase modular UPS, 11-minute runtime, low cabinet with the following features: 

 

  • Powers: 10kW - 10kVA
  • Degree of protection: IP21
  • Height: 1370 mm
  • Width: 414 mm
  • Depth: 628 mm
  • Series: Trimod HE

  Politiche per la sicurezza

(modificale nel modulo Rassicurazioni cliente)

  Politiche per le spedizioni

(modificale nel modulo Rassicurazioni cliente)

  Politiche per i resi

(modificale nel modulo Rassicurazioni cliente)

The Legrand UPS model TRIMOD HE 10 is a high-efficiency uninterruptible power supply with high-frequency PWM technology, On Line Double Conversion type, through-neutral, modular architecture, possibility of redundant N+X configuration, Rated Power 10 kVA 10 kW.


 

LUPS TRIMOD HE 10 has a modular architecture, i.e., it is composed of identical modules that, operating in parallel, make up the power section of the UPS (3.4kW single-phase power modules). These power modules contained in the UPS are composed of the following functional blocks:

  • Rectifier/PFC
  • Inverter
  • Battery charger
  • Command and control logic
  • Automatic bypass circuit


     

With cabinets already prepared to accommodate different numbers of power modules, numerous configurations can be achieved. Future power expansions can be carried out on site without the need for calibration or setting work or factory modifications and, in any case, without making use of dedicated instrumentation.

 

LUPS modular TRIMOD HE 10 can be configured as a power-redundant N+X system simply by appropriately choosing the number of 3.4 kW power modules installed in the UPS cabinet. continuous out-of-tolerance, or other anomalies. The UPS has the maintenance bypass circuit inside, which can be operated by dedicated disconnect switch.

 

TRIMOD HE 10 is equipped with two input lines, one provided for the main power supply, the other to supply power to the load through a secondary line independent of the primary line. The two inputs are, as standard, interconnected, and can be made independent during installation or commissioning.

 

The batteries are lead-acid type, sealed, maintenance-free, valve-regulated, and placed inside the UPS or external battery cabinet; The battery strings, consisting of 20 elements, can be configured separately for each control module (with multiple control boards) during installation or commissioning, if required.

 

Diagnostic and shutdown software, when installed in a PC connected to the UPS, allows access to all TRIMOD HE 10 operating data, make adjustments and settings of special functions (as with the display), and control shutdown of Windows and Linux operating systems. Optional software (UPS Management Software) together with a network interface (CS141SK), enable hierarchical multiserver shutdown and remote UPS management for any operating system in a heterogeneous network (Windows, Novell, Linux, and popular Unix). LUPS can take the following measurements and display the values directly on the display:

 

Input:

 

Currents:

  • RMS value
  • Peak value
  • Crest factor

     

Voltages:

  • RMS value

     

Power:

  • Apparent
  • Active

     

The TRIMOD HE UPS has single-phase or three-phase input and output; however, the output can be set to handle the three phases in an All measurements and additional data are available on 2 SNMP slots. In addition TRIMOD HE 10 is equipped with a set of 5 static contacts, 1 RS232 service port, 1 logical contact port. independent of each other.

 

The modular architecture is of the distributed parallel type even within individual phases. The rated power that can be delivered is given by the sum of the working modules for each phase; this allows the UPS, if properly sized, to continue supplying power to the loads even in the event of failure or during the replacement of one (or more) modules. (Redundant configuration).

 

There is a by-pass circuit on each power module that automatically transfers the load directly to the primary grid without power interruption when overload, overtemperature, voltage conditions occur.

 

Batteries:

  • Battery voltage
  • Rated capacity
  • Battery current
  • Charger status
  • Remaining capacity

     

Miscellaneous:

  • Internal temperature
  • Fan speed
  • DC BUS high voltage
  • By-pass trip
  • Overheating
  • Number of battery switching
  • Number of total discharges
  • Battery operation
  • Mains operation

     

General Characteristics:

  • On-line double conversion type of operation
  • Modular, Expandable, Redundant N+X UPS structure with power modules contained in one cabinet
  • Waveform in grid operation Sinusoidal
  • Waveform in battery operation Sinusoidal
  • Type of bypass Static, electromechanical and maintenance bypass
  • Zero switching time


     

Environmental Specifications:

  • Noise level measured at 1 meter 58-62 dBA
  • Operating temperature range 0°C to +40°C
  • Storage temperature range -20°C to +50°C (excluding batteries)
  • Operating relative humidity range 0-95% non-condensing
  • Degree of protection IP20
  • Estimated use of materials from the circular economy 37%.

     

The UPS also allows the following adjustments via the display:

 

Output:

  • Voltage
  • Frequency

     

Phase Configuration:

 

Input:

  • Enable synchronization
  • Extended synchronization interval
  • By-pass
  • Enable
  • Forced
  • Intervention sensitivity
  • Eco Mode

     

Batteries:

  • Capacity
  • Thresholds
  • Max. battery life
  • Max. battery life after reserve threshold
  • Enabling battery test

     

Enabling auto-restart:

 

Output characteristics (grid operation):

  • Rated output voltage 380, 400, 415 3F+N+PE
  • Rated output power 10 kVA
  • Active power output 10 kW
  • Efficiency up to 96%.
  • Output voltage tolerance (static) ± 1%.
  • Tolerance on output voltage (dynamic 0-100%; 100-0%) ± 1%
  • Total harmonic distortion of d-output voltage on nominal linear load < 0.5%.
  • Total harmonic distortion of output voltage on nominal nonlinear load, P.F.=1 < 1 %
  • Rated output frequency 50 Hz or 60Hz

     

Output characteristics (battery operation):

  • Rated output voltage 380, 400, 415 3F+N+PE
  • Rated output power 10 kVA
  • Active power output 10 kW
  • Output voltage tolerance (static) ± 1%.
  • Total harmonic distortion of output voltage on nominal linear load < 0.5 %.
  • Total harmonic distortion of output voltage on nominal nonlinear load < 1 %.
  • Rated output frequency 50 Hz or 60Hz (autosensing)
  • Tolerance on output frequency ± 1%
  • Allowable crest factor on output current 3:1 in accordance with IEC 62 040-3

     

Battery and charger characteristics:

  • Battery type Lead-acid, sealed, maintenance-free
  • Unit capacity Based on autonomy
  • Rated UPS battery voltage 240 volts
  • Type of high-performance PWM battery charger, one for each power module
  • Smart Charge curve, advanced 3-stage cycle
  • Rated battery charging current 2.5 A for each power module

  • Brand
  • Reference
    LEG 310442
  • In stock
    4 Items
  • EAN13
    3414970328274

  • Type
    Uninterruptible Power Supply UPS
  • Rated Power
    10000VA
  • Active Power
    10000W
  • Endurance
    11 minutes