Notifier 1-channel, high-sensitivity, CPR EN54-20 certified aspirating smoke detector. Ideal for applications requiring early detection in critical or harsh environments, with the following features:
High-sensitivity optical smoke detector (9 programmable levels from 0.06% to 6% obs/m)
Suction system with internal fan and dedicated piping up to 100 m
Interfaceable via Notifier addressed analog loop
CPR certified - EN 54-20, Classes A, B, C (max. 32 holes per system)
Ultrasonic flow sensor and LED bar for continuous visual monitoring
Dedicated alarm and fault relays for each channel
USB input for configuration via PIPE IQ LT software
(modificale nel modulo Rassicurazioni cliente)
(modificale nel modulo Rassicurazioni cliente)
(modificale nel modulo Rassicurazioni cliente)
The FAAST LT-200 FL20 intake system is designed for environments where conditions are critical or difficult to monitor with traditional detectors. It draws air from sampling holes along dedicated piping and analyzes it to identify the presence of smoke at even the lowest levels.
With very early warning detection, it is perfect for environments with sensitive equipment, such as data centers, electrical panels, archives and museums, as well as tunnels, industrial environments and hard-to-maintain areas.
The system is prepared for quick installation with removable terminals and IP65 enclosure. Includes replaceable filters, internal fan and protected electronics. Programming is done via PipeIQ LT software via built-in USB port.
Reliable and certified according to EN54-20
Simple to install and configure
Maximum sensitivity even at low smoke concentrations
Quick maintenance and front access
Direct integration with Notifier control panels via Loop
FL-IF-6: Pack of 6 replacement filters
Ø25 mm or Ø27 mm piping and fittings
Compatible with PIPE IQ LT software v2.9.1 or higher
Data centers and server rooms
Archives, museums, libraries
Electrical panels and technical cabinets
Industrial and logistics facilities
Low-maintenance or aesthetically sensitive environments
| Power supply | 18.5 31.5 VDC |
| Operating current | 170 mA (typical) 360 mA (maximum) |
| Loop current (stand-by) | max 900 µA |
| Channels | 1 channel with 1 sensor |
| Max. tube length | 100 m (Class C) |
| Max number of holes per tube | 18 (32 total per system) |
| Sensitivity range | 0.06% to 6% obs/m |
| Event memory | Up to 2240 events |
| Relays | 2 per channel (Alarm / Fault) |
| Operating temperature | -10°C TO +55°C |
| Humidity | 10% - 93% (non-condensing) |
| Degree of protection | IP65 |
| Dimensions | 403 x 356 x 135 mm |