LC1D09BD is a compact 3-pole TeSys D contactor from Schneider Electric for motor applications. Rated 9 A AC-3 4 kW at 400 V, it includes a 24 V DC coil and 1NA+1NC auxiliary contacts. Can be used in safety applications due to the certified NC mirror contact. Compact, DIN-rail-mounted, it ensures high reliability and durability. Available worldwide, it is certified to various standards (IEC, UL, CSA, CCC, EAC, for use in marine environments) and is Green Premium (RoHS/REACH) compliant.
Advantages:
- Compact product, 45 mm wide, for DIN rail and panel mounting.
- Separation between power and control circuits, easy front access to coil and auxiliary contact connections.
- Equipped with a 24 V DC coil for easy integration into all control systems.
- Features 2 built-in 1NA+1NC auxiliary contacts.
- High electrical endurance, guaranteed for 2 million cycles at 9 A AC-3 440 V
Rated operating voltage:
- <= 690 V "AC" 25...400 Hz Power circuit
- <= 300 V DC Power circuit
Rated use current:
- 9 A 60 °C) "AC" AC-3 for Power circuit at <= 440 V
- 25 A 60 °C) "AC" AC-1 for Power circuit at <= 440 V
- 9 A 60 °C) "AC" AC-3e for Power circuit at <= 440 V
Motor power:
- 2.2 kW at 220...230 V "AC" "50/60 Hz" (AC-3)
- 4 kW at 380...400 V "AC" "50/60 Hz" (AC-3)
- 4 kW at 415...440 V "AC" "50/60 Hz" (AC-3)
- 5.5 kW at 500 V "AC" "50/60 Hz" (AC-3)
- 5.5 kW at 660...690 V "AC" "50/60 Hz" (AC-3)
- 2.2 kW at 400 V "AC" "50/60 Hz" (AC-4)
- 2.2 kW at 220...230 V " AC" "50/60 Hz" (AC-3e)
- 4 kW at 380...400 V "AC" "50/60 Hz" (AC-3e)
- 4 kW at 415...440 V "AC" "50 /60 Hz" (AC-3e)
- 5.5 kW at 500 V "AC" "50/60 Hz" (AC-3e)
- 5.5 kW at 660...690 V "AC" "50/60 Hz" (AC-3e)
Motor power in hp:
- 1 hp at 230/240 V for 1 phase motors" AC" "50/60 Hz"
- 2 hp at 200/208 V for 3 phase motors" AC""50/60 Hz"
- 2 hp at 230/240 V for 3 phase motors" AC" "50/60 Hz"
- 5 hp at 460/480 V for 3 phase motors" AC" "50/60 Hz"
- 7.5 hp at 575/600 V for 3 phase motors" AC" "50/60 Hz"
- 0.33 hp at 115 V for 1 phase motors" AC""50/60 Hz"
Conventional thermal current in open air:
- 25 A at <60 °C for Power circuit
- 10 A at <60 °C per signaling circuit
Rated Closing Power:
- 250 A at 440 V for Power circuit in accordance with IEC 60947
- 140 A "AC" for signaling circuit complying with IEC 60947-5-1
- 250 A DC for signaling circuit complying with IEC 60947-5-1
Rated short-time allowable current:
- 105 A at <40 °C - 10 s for Power circuit
- 210 A at <40 °C - 1 s for Power circuit
- 30 A at <40 °C - 10 min for Power Circuit
- 61 A at <40 °C - 1 min for Power circuit
- 100 A - 1 s per signaling circuit
- 120 A - 500 ms per signaling circuit
- 140 A - 100 ms per signaling circuit
Associated fuse gauge:
- 10 A gG for signaling circuit complying with IEC 60947-5-1
- 25 A gG at <= 690 V coordination Type 1 for Power circuit
- 20 A gG at <= 690 V coordination Type 2 for Power circuit
Power dissipation per pole:
- 1.56 W AC-1
- 0.2 W AC-3
- 0.2 W AC-3e
Rated insulation voltage:
- 690 V complying with IEC 60947-4-1 Power circuit.
- 600 V CSA certified Power circuit
- 600 V UL certified Power circuit
- 690 V complying with IEC 60947-1 signaling circuit
- 600 V CSA certified signaling circuit
- 600 V UL certified signaling circuit
Dimensions and weight:
- Height: 77 mm
- Width: 45 mm
- Depth: 86 mm
- Weight: 320 grams