ComPacT NSX is designed to optimize space and interruption capacity for all standard and specific applications.
Strengths:
- This base frame is supplied without a breaker, and is compatible with any type of breaker to be ordered separately
- Icu interrupting capacity is 50kA at 415VAC 50/60Hz
- Operating voltage is 690VAC 50/60Hz (limited to 440VAC 50/60Hz if differential protection is present)
- Can be equipped with a variety of optional functions and accessories
- Dimensions are 140mm x 161mm x 86mm
- Ensures compliance with international standards (IEC 60947), CCC, EAC and maritime specifications
- ComPacT NSX160N is part of the Schneider Electric EcoStruxure Power architecture
- Schneider Electric unmistakable green style for the entire ComPacT range
- Estimated 40% reduction in wiring time for panel builders
- Experience easier installation with new ergonomic front plate design
- Get assurance that all auxiliaries are in the right place and check that you have the right coil rating
- New ergonomic lever for easy manual switch operation
Features:
- Range: Next-generation ComPacT
- Insulation suitability: yes compliant with EN/IEC 60947-2
- Utilization category: A
- Control Type: On/Off
- Mounting mode: Fixed
- Elevation connection: Front
- Negative connection: Front
- Connection pitch: 35 mm
- Mechanical durability: 40000 cycles in accordance with IEC 60947-2
- Dimensions: height 161mm - width 140mm - depth 86mm
- Ambient air temperature for operation: -25/+70 degrees
- Ambient air temperature for storage: -50/+85 degrees
Rated maximum short-circuit breaking capacity:
- 10 kA at 600 V AC 50/60 Hz in accordance with UL 508 - 85 kA at 240 V AC 50/60 Hz in accordance with UL 508
- 10 kA Icu at 660/690 V AC 50/60 Hz complying with IEC 60947-2
- 35 kA Icu at 525 V AC 50/60 Hz complying with IEC 60947-2
- 50 kA at 480 V AC 50/60 Hz complying with UL 508
- 36 kA Icu at 500 V AC 50/60 Hz complying with IEC 60947-2
- 50 kA Icu at 380 /415 V AC 50/60 Hz complying with IEC 60947-2
- 50 kA Icu at 440 V AC 50/60 Hz complying with IEC 60947-2
- 90 kA Icu at 220/240 V AC 50/60 Hz complying with IEC 60947-2
Rated service short-circuit breaking capacity:
- 10 kA at 660/690 V AC 50/60 Hz complying with IEC 60947-2
- 35 kA at 525 V AC 50/60 Hz complying with IEC 60947-2
- 36 kA at 500 V AC 50/60 Hz complying with IEC 60947-2
- 50 kA to 380/415 V AC 50/60 Hz complying with IEC 60947-2
- 50 kA at 440 V AC 50/60 Hz complying with IEC 60947-2
- 90 kA at 220/240 V AC 50/60 Hz complying with IEC 60947-2
Electrical durability:
- 40000 cycles 440 V AC 50/60 Hz In/2 complying with IEC 60947-2
- 15000 cycles 690 V AC 50/60 Hz In/2 complying with IEC 60947-2
- 20000 cycles 440 V AC 50/60 Hz In complying with IEC 60947-2
- 7500 cycles 690 V AC 50/60 Hz Compliant with IEC 60947-2