Rated service interrupting capacity:
- 20 kA at 440 V "AC" "50/60 Hz" complying with IEC 60947-2
- 25 kA at 380/415 V "AC" "50/60 Hz" complying with IEC 60947-2
- 40 kA at 220/240 V " AC" "50/60 Hz" complying with IEC 60947-2
- 15 kA at 500 V "AC" "50/60 Hz" complying with IEC 60947-2
Electrical life:
- 40000 cycles 440 V "AC" "50/60 Hz" In/2 complying with IEC 60947-2
- 15000 cycles 690 V "AC" "50/60 Hz" In/2 complying with IEC 60947-2
- 20000 cycles 440 V "AC" "50/60 Hz" In complying with IEC 60947-2
- 7500 cycles 690 V "AC" "50/60 Hz" In complying with IEC 60947-2
Other technical characteristics:
- Pollution degree: 3 in accordance with IEC 60664-1
- IP degree of protection: IP40 in accordance with IEC 60529
- IK degree of protection: IK07 in accordance with IEC 62262
- Mounting bracket: Back plate
- Upper mountings: Front side
- Bottom connections: Front side
- Connection pitch: 35mm
- Dimensions: height 161mm - width 140mm - depth 86 mm