Measurement of voltage inputs:
- Rated voltage (Ue): phase-phase VAC 600 - phase-neutral VAC 300
- Operating voltage range: phase-phase VAC 50...720 - phase-neutral VAC 30...360
- Measurement method of voltage inputs: True RMS
- Connection method: Separate. two. three-phase with or without neutral. balanced three-phase system
Current inputs:
- Current rating (Ie) UN 1A/5A
- Current reading by Rogowski coils: UN 20...6300
- Measuring range: 0.01...1.2 / 0.01...6
- Measurement method : TRMS
- Overload capacity: +20% Ie from external CT with secondary 5A
- Peak overload: UN 50A for 1s
Accuracy:
- Measurement conditions (T +23°C ±1°C / Relative humidity 45 ±15% RH)
- VNL voltage: ±0.5%
- VLL voltage: ±0.5%
- Current: ±0.5%
- Frequency: ±0.05%
- Active power: ±0.5%
- Active energy: Class 1 (IEC/EN/BS 62053-21)
- Reactive energy: Class 2 (IEC/EN 62053-23)
Insulations:
- IEC/EN rated insulation voltage Ui: 600V
- Rated impulse withstand voltage Uimp kV 9.5
- Withstand voltage at operating frequency: kV 5.2
- Harmonic analysis 15th order
- PLC logic: NO
- RS485 communication port type
- Ethernet-RS485 gateway function NO
Mechanical characteristics:
- Type of housing: Polyamide
- Type of terminals: Removable
- Conductor cross-section: min mm² 0.2 - Maximum mm² 2.5
- Min AWG 24 - Maximum AWG 12
- Tightening torque (Max) - Nm 0.5 - lbin 4.5
- Fixing: flush mounting
- Weight: 350 grams
Environmental conditions:
- Operating temperature: -20/+60°C
- Storage temperature: -30/+80°C
- Relative humidity %: <90
- Maximum pollution degree: 2
- Degree of protection: IP54