• Double Insulation Flameproof Cable 1X35mmq 1 Meter FG16R161X35

Double Insulation Flameproof Cable 1X35mmq 1 Meter FG16R161X35

€5.33
Tax included

Double Insulation Flameproof Cable 1X35mmq 1 Meter FG16R161X35 without yellow/green

 

Diameter: 13mm

 

Sold by the meter.

  Politiche per la sicurezza

(modificale nel modulo Rassicurazioni cliente)

  Politiche per le spedizioni

(modificale nel modulo Rassicurazioni cliente)

  Politiche per i resi

(modificale nel modulo Rassicurazioni cliente)

Reference IEC Guide 20-67 as applicable: FG16OR cable is suitable for power supply in industry, construction sites, residential construction. For indoor and outdoor fixed laying, even in wet environments; for direct and indirect underground laying. For outdoor installation, on masonry and metal structures, on walkways, pipes, ducts and similar systems. Suitable for bundle installations in environments with higher risk in case of fire.

 

Reference Construction Products Regulation 305/2011 EU and Standard EN 50575: Given the properties of limiting fire development and heat emission, the cable is suitable for power supply in buildings and other civil engineering works.

 

Description:

  • Conductor: red copper, flexible formation, class 5
  • Insulation: rubber, G16 quality
  • Filler: thermoplastic, penetrating between cores (only in multi-core cables)
  • Sheathing: PVC, R16 quality
  • Color: gray

Functional characteristics:

  • Rated voltage Uo/U: 600/1000 V AC 1500 V DC.
  • Maximum Um voltage: 1200 V ac 1800 V dc also to earth
  • Industrial test voltage: 4000 V
  • Maximum operating temperature: 90°C
  • Minimum operating temperature: -15°C (in the absence of mechanical stress)
  • Maximum short-circuit temperature: 250°C

Good resistance to industrial oils and greases. Good behavior at low temperatures. Resistant to UV radiation

 

Laying conditions:

  • Minimum laying temperature: 0°C
  • Recommended minimum bending radius: 4 times the cable diameter
  • Maximum recommended tensile stress: 50 N/mm2 of copper cross section

Reactions to Fire: Complies with CPR REGULATION 305/2011/EU:

  • Standard: EN 50575:2014+A1:2016
  • Class: cca-s3, d1, a3
  • Classification: (IEC UNEL 35016) EN 13501-6
  • Heat and smoke emission and flame development EN 50399
  • Non-propagation of flame: EN 60332-1-2
  • Corrosive and halogenated gases: EN 60754-2
  • Notified Body: 0051 - IMQ

 

 

  • Brand
  • Reference
    9X9 FG16R1X35
  • In stock
    13201 Items

  • Colour
    Grey
  • Cross-Section
    35mmq
  • With yellow/green
    No