Reference Guideline CEI 20-67 as far as applicable: FG16OR cable is suitable for power supply in industry, construction sites, residential buildings. For fixed installation indoors and outdoors, even in wet environments; for direct and indirect underground laying. For installation in the open air, on masonry and metal structures, on walkways, pipes, ducts and similar systems. Suitable for bundle installations in environments with increased fire risk.

 

Reference Construction Products Regulation 305/2011 EU and Standard EN 50575: Due to its properties of limiting the development of fire and the emission of heat, the cable is suitable for power supply in buildings and other civil engineering works.

 

Description:

  • Conductor: red copper, flexible formation, class 5
  • Insulation: rubber, G16 quality
  • Filler: thermoplastic, penetrating between the cores (only in multi-core cables)
  • Sheath: PVC, R16 quality
  • Colour: grey

 

Functional characteristics:

  • Rated voltage Uo/U: 600/1000 V AC 1500 V DC
  • Maximum voltage Um: 1200 V AC 1800 V DC also to earth
  • Industrial test voltage: 4000 V
  • Maximum operating temperature: 90°C
  • Minimum operating temperature: -15°C (in the absence of mechanical stress)
  • Maximum short-circuit temperature: 250°C

Good resistance to industrial oils and greases. Good behaviour at low temperatures. UV resistant

 

Laying conditions:

  • Minimum laying temperature: 0°C
  • Recommended minimum bending radius: 4 times the cable diameter
  • Recommended maximum tensile stress: 50 N/mm2 of copper section

 

Reactions to fire: Compliant to CPR REGULATION 305/2011/EU:

  • Standard: EN 50575:2014+A1:2016
  • Class: Cca-s3, d1, a3
  • Classification: (IEC UNEL 35016) EN 13501-6
  • Heat and smoke emission and flame development EN 50399
  • Non-propagation of flame: EN 60332-1-2
  • Corrosive and halogenated gases: EN 60754-2
  • Notified Body: 0051 - IMQ