Single-core cable AUE4CR 1x10 + 6C for fixed installation, XLPE insulated and PVC sheath, with the following characteristics:
Formation: 1x10 mm² + 6C
Conductor diameter: 3.5 mm
Insulation thickness: 1.2 mm
Sheath thickness: 1.4 mm
Max outer diameter: 13.2 mm
Electrical resistance at 20 degrees: 3.08 /km
Nominal voltage: 0.6/1 kV
ENEL registration number: 330101
The sale price is per metre.
(modificale nel modulo Rassicurazioni cliente)
(modificale nel modulo Rassicurazioni cliente)
(modificale nel modulo Rassicurazioni cliente)
The single-core cable AUE4CR is designed for low voltage (0.6/1 kV) energy transport and complies with the standards required for ENEL supplies. Made with a class 2 rigid aluminium conductor and a concentric copper conductor, it ensures excellent performance in both indoor and outdoor installations.
Phase conductor: Rigid aluminium (10 mm²)
Concentric conductor (neutral/screen): Red copper wires (6 mm²) with counter spiral tape
Sheath: Rz quality PVC
Sheath colour: Grey
This combination of materials ensures mechanical strength, flexibility, and durability over time, even in challenging environmental conditions.
The AUE4CR cable is suitable for fixed laying in trays, pipes, or channels, both indoors and outdoors. It can also be buried, according to current regulations. The minimum bending radius is 14 times the outer diameter of the cable, ensuring flexibility during installation.
| Nominal voltage | Uo/U = 0.6/1 kV |
| Maximum operating temperature (phase conductor) | 90°C |
| Maximum concentric conductor temperature | 85°C |
| Minimum operating temperature | –15°C |
| Maximum short circuit temperature | Phase conductor: 250°C – Concentric conductor: 160°C |
| Minimum bending radius | 14 × Ø outer |
| ENEL registration number | 330101 |
| Formation | 1 × 10 mm² + 6C |
| Conductor Ø | 3.5 mm |
| Insulation thickness | 1.2 mm |
| Sheath thickness | 1.4 mm |
| Max outer Ø | 13.2 mm |
| Indicative weight | 170 kg/km |
| Electrical resistance at 20°C | 3.08 Ω/km |
| Current carrying capacity at 30°C | In air: 64 A – In pipe in air: 57 A – Buried: 68 A |
| Thermal short circuit current (1 s) | Phase conductor: 0.9 kA – Neutral conductor: 0.8 kA |