FG16OH2R16 multi-core shielded cable, anti-interference shielding, high safety and strength for industrial and civil fixed installations, with the following characteristics:
Section: 4x10 sq. mm
Rated voltage: 0.6/1 kV
Conductor diameter: 4 mm
Insulation thickness: 0.7 mm
Sheath thickness: 1.8 mm
Outer diameter: 19.2 mm
Max. electrical resistance (20°C): 1.91 /km
Current rating in air (30°C): 60A
Current rating buried (20°C): 55A
Sold by the meter.
(modificale nel modulo Rassicurazioni cliente)
(modificale nel modulo Rassicurazioni cliente)
(modificale nel modulo Rassicurazioni cliente)
FG16OH2R16 4x10 sq mm shielded multi-core cable is designed for fixed-lay applications in civil and industrial electrical installations where protection against electromagnetic interference is required. The braided shielding of red copper wires ensures high noise immunity, making it particularly suitable in environments where power and signal networks coexist.
The cable consists of:
Class 5 annealed red copper flexible conductors
High-modulus ethylpropylene rubber insulation (G16) with excellent mechanical and thermal characteristics
Non-hygroscopic filler for perfect cohesion between components
Red copper braid screen for EMI protection
R16 PVC outer sheath, resistant to shock, abrasion and weathering
All in a 4-conductor multipole configuration with gray sheathing, according to HD 308 standard for core color code.
Thanks to the fire reaction class Cca-s3, d1, a3, the cable complies with the Construction Products Regulation (CPR), ensuring good resistance to flame propagation, low smoke emission and no glowing drops, contributing to the safety of public, residential and industrial buildings.
The cable is suitable for:
Indoor, outdoor and wet fixed installations
Laying on masonry, metal structures, conduits, pipes or directly underground
Power distribution in residential, commercial, industrial and tertiary installations
Applications requiring reduction of electromagnetic interference (EMI)
| Parameter | Value |
|---|---|
| Conductor cross section | 4x10 sq. mm |
| Rated voltage | 0.6/1 kV |
| Conductor | Annealed red copper, class 5 |
| Insulation | Ethylpropylene rubber G16 |
| Outer sheath | PVC R16, gray color |
| Shielding | Red copper braid |
| Reaction to fire (CPR) | Cca-s3, d1, a3 |
| Conductor diameter | 4 mm |
| Insulation thickness | 0.7 mm |
| Sheath thickness | 1.8 mm |
| Outer diameter | 19.2 mm |
| Max. electrical resistance (20°C) | 1.91 Ω/km |
| Operating temperature | -15°C TO +90°C |
| Max short circuit temperature | 250°C (≤240 mm²) / 220°C (>240 mm²) |
| Minimum laying temperature | 0°C |
| Maximum tensile stress | 50 N/mm² |
| Minimum bending radius | 8 x outer diameter |
| Current carrying capacity in air (30°C) | 60 A |
| Current carrying capacity underground (20°C) | 55 A |