In the device software there is a diagnostic and repair algorithm for the voltmeter and ammeter insertion sequence. The function can be activated on demand with a password and allows the wiring sequence to be viewed and changed via software provided the following conditions are met:
- The neutral conductor (in the 4-wire network) is correctly placed at the corresponding terminal (normally number 11)
- There are no crossings of conductors between different CTs (e.g., on phase 1 of the device there is a wire from CT 1 and on the other a wire from CT 2)
- The power factor is between 1 and 0.5 Inductive for each phase
Auxiliary power supply:
- Rated value Uaux ca: 80...265V
- Rated frequency fn: 50 opp. 400Hz (automatic selection)
- Operating frequency: 4565Hz (fn 50Hz) opp. 360...440Hz (fn 400Hz)
- Self-consumption: 2.5VA (230Vac backlight 30% without external modules)
- Uaux dc nominal value: 110...300Vdc
- Self-consumption: 3.5W (without modules, 110Vdc)
- Reverse polarity protection
Insulation:
- Installation category: III
- Pollution degree: 2
- Insulation reference voltage: 300V (phase to neutral)
Environmental conditions:
- Reference temperature: 23°C ± 2°C
- Specified operating range: -5...55°C
- Limiting range for storage and transportation: - 25...70°C
- Suitable for use in tropical climates
- Maximum power dissipation 1: ? 5W For thermal sizing of switchgear
Enclosure:
- Enclosure: recessed (panel cut-out 92x92mm)
- Front panel: 96x96mm
- Depth: 62mm
- Maximum depth: 81mm (with optional modules)
- Connections: screw fixing terminals (current inputs) pull-out (voltage inputs)
- Housing material: self-extinguishing polycarbonate
- Degree of protection (EN60529): IP54 front panel, IP20 terminals
- Weight: 285 grams