Elkron FAP541 Microprocessor Control Panel 1 Line Modular LOOP, i.e., they come in a standard configuration with the possibility of peripheral and function expansion. It is possible to have from a minimum of 1 up to a maximum of 16 addressed loops:
- Ability to manage up to 128 points max.
- Self-learning of devices in the field
- Backlit display 4 x 40 characters
- History log: 1,000 events
- Chronological viewable directly from display
- 10 passwords programmable on 3 levels 480
- Programmable zones, 240 groups of zones, 240 groups of points
- USB port for local PC connection for programming via dedicated software
- Ability to monitor sensor signal-to-noise ratio level
- Built-in real time clock with battery backup
- Non-volatile memory
- Central unit outputs: alarm, siren, fault, programmable (power failure/exclusion)
- Internal buzzer
- Single point/zone exclusion
- Power supply: 230Vac
- Maximum deliverable current: 1.5A@24Vdc
- Limitation of battery charge and control of battery status
- Accumulator housing: 2 batteries of 12 @12Vdc
- Possibility of making loops max 2km with 2x1.5mm shielded cable
- Noise immunity up to 30Vm
- Common dialogue protocol for all system control panels
- Dimensions: 490 (W) x 350 (H) x 145 (D) mm
- EN54 part 2 and 4 certified (0051-CPD-0240)