The S300P series circuit breakers provide protection in industrial plants against overloads and short circuits. This product is manufactured according to international IEC and UL standards, for markets where it is required.
The C curve, trip threshold of 5 to 10 times In, for ohmic-inductive circuit application with medium inrush currents. It is widely used in domestic installations.
It protects the system from overloads and short circuits, guaranteeing maximum reliability and operational safety.
A thermal-magnetic circuit breaker is a safety device that can automatically (i.e. without external intervention) interrupt the flow of electrical current in an electrical circuit in the event of an overcurrent.
Connection capacity: Bar 10 / 10 mm²:
- Flexible with ferrule 0.75...25 mm²
- Flexible 0.75...25 mm²
- Flexible 0.75...25 mm²
- Rigid 0.75...35 mm² Stranded 0.75...35 mm²
- Stranded 0.75 ... 35 mm²
Other technical characteristics:
- Power connection: Arbitrary
- Contact position indication: Red ON / Green OFF
- Electrical resistance: 10000 AC cycle
- Mechanical resistance: Cycle 20000
- Overvoltage category: IV
- Rated operating voltage: acc. to IEC 60898-1 415 V AC - acc. to IEC 60898-1 415 V - acc. to IEC 60947-2 415 V AC
- Operating voltage: Maximum (tolerance included) 457 V AC - Maximum 457 V AC - Minimum 12 V AC - Minimum 12 V DC
- Tightening torque: 2.8 Nm
- Type of screw terminal: Fault-tolerant bi-directional cylinder lifting terminal
- Actuator marking: I/O
- Actuator material: Insulation group II, black, sealable
- Housing material: Insulation group I, RAL 7035
- DIN rail mounting: TH35-15 (mounting rail 35 x 15 mm) acc. to IEC 60715 -TH35-7.5 (mounting rail 35 x 7.5 mm) acc. to IEC 60715
- Mounting position: Any
- Recommended screwdriver: Pozidrive 2
- Standard: CSA 22.2 No. 235 -CEI/EN 60898-1 -CEI/EN 60947-2 -UL1077
- Installation dimensions: acc. to DIN 43880 1
- Stripping length of cable: 14 mm
- Terminal type: Screw terminals
- Ambient air temperature: Operating -40 ... +70 °C - Storage -55 ... +70 °C
- Degree of protection: IP20 - Enclosure with cover IP40
- Pollution degree: 3
- Environmental conditions: 28 cycles at 55 °C / 90-96 % and 25 °C / 95-100 %
- Vibration resistance: 20 cycles with 0.8 In Load: 5g 5...150...5 Hz
- Shock resistance acc. to IEC 60068-2-27: 25 g 3 shocks 18 ms
- Dimensions: Width in number of modular spaces: 4
- Net product width: 70 mm
- Net product height: 88 mm
- Depth / net product length: 69 mm
- Built-in depth ( t 2 ): 69 mm